Life Safety Code Survey Trends Report – October 2026
In October, the Iowa Department of Inspections, Appeals & Licensing completed 37 recertification surveys. 35 of the 37 received deficiencies averaging 4.1. Two of the recertifications were deficiency free.
Congratulations to Sunrise Retirement Community on a deficiency free life safety code survey!
With emergency preparedness, the most frequently cited deficiency continues to be E039 cited 7 times related to conducting emergency preparedness drills. This deficiency is cited when nursing homes fail to complete a full-scale community-based drill and/or an additional exercise which can be a full-scale exercise or a tabletop. One of the deficiencies included non-compliance as the nursing home didn’t document their efforts to participate in a community-based drill or complete a post-exercise analysis.
For life safety, the highest cited deficiency was K918 related to generator testing and inspection followed by K353 sprinkler system maintenance and testing, K291 emergency light testing, K712 fire drills, and K920 electrical systems – other. Here are some examples of deficiencies cited during the surveys:
K918:
- Missing 1.5 hour load bank test for a diesel generator in the last 12 months.
- Missing monthly testing.
- Missing weekly inspections.
- Documentation for weekly inspections lacked:
- Battery
- Belts
- Hoses
- Documentation for monthly tests lacked:
- Conductivity testing of the generator battery.
- Amperage at each leg
- Meter readings
- Annual diesel fuel quality test wasn’t completed.
- Missing annual testing and inspection of the EES main and feeder circuit breakers.
- Didn’t have natural gas reliability letter.
- Monthly testing wasn’t for a full 30-minutes.
- Transfer of power was more than 10 seconds.
K353:
- Missing quarterly sprinkler system inspections.
- Corroded sprinkler heads.
- Dry sprinkler heads weren’t tested or replaced every 10 years.
- Quick response sprinkler heads weren’t tested or replaced every 50 years.
- Escutcheon rings were missing from the sprinkler heads.
- Missing 5-year internal obstruction sprinkler system inspection.
- Missing 3-year testing and inspection of dry sprinkler system.
- Sprinkler heads were dusty or had paint spackle on them.
- Deficiencies identified during the sprinkler system inspection weren’t repaired.
K291:
- Missing documentation of monthly functional testing and/or annual 90-minute testing of emergency lights.
- The medication room light was able to be operated by a light switch and failed to have additional emergency light installation.
- No emergency light was present near the backup generator.
K712:
- Fire drills were missing.
- Staff didn’t sign when they participated in a drill.
- Drills were conducted at approximately the same time
- The monitoring company wasn’t contacted when the drill was conducted to ensure they received the alarm signal.
- Documentation didn’t include:
- Start and stop times of the drills.
- Monitoring center operator name or number.
K920:
- Use of unapproved surge protectors.
- Prohibited items plugged into surge protectors.
- Use of extension cords.
- Multi-plug adaptors were used.